Exit Lighting

Testing of Exit & Emergency Lights, AS/NZS 2293.2:1995 states that both Exit and Emergency Lighting MUST be Inspected and Serviced by a trained technician
EVERY SIX MONTHS


Six Monthly Procedures

  1. Replace any faulty lamps prior to the test procedure. Note, when replacing a faulty lamp it is advisable to replace the lamp starter also.
  2. Operate the fitting from their battery supply by turning off their normal power supply. You will see one tube within the fixture go out and the other tube illuminate.
  3. The light must remain alight for at least 90 minutes.
  4. Replace any faulty lamps or fittings. Note, depending upon the nature of the fault, fittings can be repaired. But the cost of fault diagnosis and repair can, more often than not, exceed the cost of the provision of a new fitting.
  5. Turn on the normal lighting power supply and check that the battery charger indicator light on  the fitting functions correctly.
  6. Record details of the test and correct operation of the system. Record the replacement of faulty lamps and the repair or replacement of fittings.






                                                                                                                                         – Penalty table –

Code

Offence

Legislation

Penalty Units

Company Fine

4215

Fail to produce a certificate of Maintenance of special fire service to authorised fire officer

Reg 15(4)

5

$375.00

4234

Fail to maintain to a standard of safety and reliability a prescribed fire safety installation namely......

Act 104D(1)

50

$3750

4235

Remove prescribed fire door

Act 104D(1) 1851

50

$3750

4236

Fail to maintain fire door installation

Act 104D(1) 1905.1

50

$3750

4237

Fire door/smoke door fail to return to the fully closed position

Act 104D(1)/ BCA

50

$3750

4238

Fix fire doors in open position

Act 104D(1)/ BCA

50

$3750

4239

Fail to display prescribed Hose Reel sign

Act 104D(1)/AS 2441

50

$3750

4240

Fail to display prescribed Fire Extinguisher Sign

Act 104D(1)/AS 2444

50

$3750

4241

Fail to provide site plan of fire extinguishers

Act 104D(1)/AS1851

50

$3750

4242

Fail to provide unique site identification mark on extinguisher

Act 104D(1)/AS1851

50

$3750

4243

Fail to recharge/replace prescribed Fire Extinguisher

Act 104D(1)/AS1851

50

$3750

4244

Cover/obstruct prescribed Fire Extinguisher

Act 104D(1)/AS 2444

50

$3750

4245

Cover/obstruct prescribed equipment Hose Reel

Act 104D(1)/AS2441

50

$3750

4246

Cover/obstruct prescribed Fire Extinguisher Sign

Act 104D(1)/AS1851

50

$3750

4247

Cover/obstruct prescribed Hose Reel Sign

Act 104D(1)/AS 2441

50

$3750

4251

Cover/Obstruct prescribed Exit Light

Act 104(D)1/AS 2293.1

50

$3750.00

4252

Cover/Obstruct prescribed Emergency Light

Act 104(D)1/AS 2293.1

50

$3750.00

 

 

1407 | Website Developed by MyWork Australia
Home | About Us | Shop | Products & Services | Test & Tag | Exit & Emergency | Testimonials | Gallery | Links | Contact Us |